What should be Paid Attention to When Using the Magnetic Flap Level Gauge?
Some comments on the use of the Magnetic Flap Level Gauge:
1. Before use, calibrated magnetic steel shall be used to set the balls below zero into red and other balls into white;
2. Open the bottom flange and install the magnetic float (note: the magnetic end of the heavy end shall be upward, not inverted.) ;
3. Debugging should open the upper guide tube valve, then slowly open the bottom valve, pressure check, make medium smoothly into the main pipe (sharp shock should be avoided in the operation of the media float, cannot cause float column fluctuations, impact shows accuracy), the magnetic turn red and white ball is normal, then close the tube valve, open the drain valve, let the led tube liquid level drops, this method for three times, it is normal, can be put into operation (except for corrosion resistance and other special liquid)
4. The magnetic tiller level gauge must be installed vertically. Ball valves shall be installed between the magnetic tiller level gauge and the vessel primer for easy maintenance and cleaning; The installation position of the liquid level meter should be avoided or far away from the inlet and outlet of the material medium to avoid rapid changes in the local area of the material fluid and affect the accuracy of the liquid level measurement.
5. Remove impurities by unscheduled cleaning of the main pipe according to the media conditions;